BTU / kW Conversion Reference

Conversion factors and a quick-lookup table between kW, watts, BTU/h, refrigeration tons and kcal/h — the five units cooling-capacity nameplates and datasheets typically mix between regions. Use alongside the BTU / kW Converter.

Last updated: June 2026

Terms

CRACComputer Room Air Conditioner
The specialized air-conditioning unit that cools a server room.
IECInternational Electrotechnical Commission
The international body that writes electrical safety standards used across most of the world outside North America. When a chart cites an IEC number, it's pointing to the official rulebook behind a calculation.

Conversion Factors

1 kW = 3 412.14 BTU/h = 0.2843 tons = 860.42 kcal/h

1 ton of refrigeration = 12 000 BTU/h = 3.517 kW

1 BTU/h = 0.293 W  |  1 kcal/h = 1.163 W

Quick Lookup — Common Cooling Capacities

kWWattsBTU/hTons (TR)kcal/h
1 kW1 0003 4120.28860
3.5 kW3 50011 9431.003 011
5 kW5 00017 0611.424 302
7 kW7 00023 8851.996 023
10 kW10 00034 1212.848 604
17.6 kW17 60060 0535.0015 145
35.2 kW35 200120 10710.0030 291
100 kW100 000341 21428.4386 042

Ton sizes (1, 5, 10 TR…) are common nameplate steps for packaged AC/CRAC units in North American markets; kW steps are more common in European/IEC datasheets.

Where Each Unit Shows Up

UnitTypically used inWatch out for
kWEuropean/IEC datasheets, electrical load calculationsCooling kW (thermal) vs electrical kW input (compressor power) are different numbers — check which one a spec sheet means
BTU/hUS/UK residential and small split-system AC nameplatesOften rounded to marketing numbers (9 000 / 12 000 / 18 000 BTU/h)
Tons (TR)North American commercial/packaged HVAC, chillers"Ton" here means a unit of cooling power, not a unit of mass — historically the heat to melt one short ton of ice in 24 h
kcal/hOlder European, Japanese and some Asian-market HVAC datasheetsIncreasingly replaced by kW on modern equipment, but still common on legacy nameplates

Frequently Asked Questions

Why do AC units list both BTU/h and kW?

Many international manufacturers sell into both BTU/h-native markets (US, parts of Asia) and kW-native markets (Europe). Listing both avoids needing region-specific datasheets, and lets installers cross-check a nameplate value against local design documents in whichever unit they normally use.

Is "1 ton of cooling" related to weight?

Only historically. A refrigeration ton originally meant the cooling power needed to freeze one short ton (2 000 lb) of water into ice in 24 hours — about 12 000 BTU/h. Today it's used purely as a cooling-capacity unit, with no weight measurement involved.

Is the cooling kW the same as the electrical kW the unit draws?

No — they're often very different. Cooling kW (thermal output) divided by electrical kW (compressor input) gives the unit's coefficient of performance (COP) or EER. A unit might output 10 kW of cooling while drawing only 3–4 kW of electricity (COP ≈ 2.5–3.3). Always check which figure a datasheet quotes before sizing electrical infrastructure.

How does this relate to the Cooling Load Calculator?

The Cooling Load Calculator tells you how much cooling capacity (in kW) a room needs. This converter then translates that requirement, or an existing unit's nameplate rating, into whatever unit your supplier or local market uses.