Skip to content
DCIM ProfessionalsDCIM Professionals

Electrical

kVA / kW / Amps Reference

Single-phase and three-phase power formulas, typical power factor by load type, and a quick kVA-to-amps lookup at common voltages. Use alongside the kVA / kW / Amps Converter.

Last updated: June 2026

Terms

UPSUninterruptible Power Supply
A battery backup that keeps equipment running for a short time if mains power cuts out, giving generators time to start or equipment time to shut down safely.
kVAKilovolt-Ampere
A unit of electrical power, similar to kW but measured slightly differently — it includes power that's drawn but not fully put to use. Equipment ratings often use kVA because it's the more cautious, safer number to size for.

The Formulas

Three-phase: I = (kVA × 1000) ÷ (√3 × V)  |  kW = kVA × cos φ

Single-phase: I = (kVA × 1000) ÷ V

Where: I = current (A) | V = voltage — line-to-line for three-phase, line-to-neutral for single-phase | cos φ = power factor

kVA, kW and kVAR (reactive power) form the "power triangle": kVA² = kW² + kVAR².

Typical Power Factor by Load Type

Load typeTypical cos φNotes
Purely resistive (heaters, incandescent lighting)1.0No reactive component — kVA = kW
Modern IT / server PSU loads~0.95 – 0.99Active PFC supplies are close to unity power factor
Motors (induction, general)0.8 – 0.9Lower at partial load; nameplate PF is at full load
UPS / generator nameplate rating0.8 – 0.9Often quoted at 0.8 PF (older designs) or 0.9 PF (modern double-conversion)
Fluorescent/LED lighting with ballast0.85 – 0.95Varies by ballast/driver design; check datasheet PF rating

Use the nameplate power factor when known — these are planning-stage typical values, not substitutes for actual equipment data.

Three-Phase kVA → Amps Quick Lookup

At 400 V line-to-line, three-phase.

kVACurrent (A)kW at PF 0.9
10 kVA14.4 A9 kW
25 kVA36.1 A22.5 kW
50 kVA72.2 A45 kW
100 kVA144.3 A90 kW
250 kVA360.8 A225 kW
500 kVA721.7 A450 kW

Worked Example

Inputs: 100 kVA at power factor 0.9, 400 V three-phase.

Real power: kW = 100 × 0.9 = 90 kW

Current: I = (100 × 1000) ÷ (1.732 × 400) ≈ 144 A

Frequently Asked Questions

What's the difference between kVA, kW and kVAR?

kW is real power — the power that actually does useful work (heat, light, mechanical force). kVAR is reactive power — power that oscillates between source and load without doing useful work, caused by inductive/capacitive loads. kVA is apparent power — the vector sum (kVA² = kW² + kVAR²), and it's what generators, UPS and transformers are actually rated in, since their windings/conductors must carry the full apparent current regardless of power factor.

Why are UPS and generators rated in kVA, not kW?

A UPS or generator's output windings and conductors are limited by current, which is driven by apparent power (kVA), not real power (kW). A UPS rated 100 kVA at 0.9 PF delivers 90 kW of real power — running it at a load with worse power factor reduces the available real power even though the kVA capacity is unchanged.

Why does three-phase use √3?

In a three-phase system, the three line currents are 120° apart in phase. The √3 (≈1.732) factor accounts for this phase relationship between line-to-line voltage and the resulting current/power — it's a direct consequence of the vector geometry of a balanced three-phase system, not an arbitrary constant.

How does this relate to the Fuse & Breaker Sizing tool?

This converter gives you the design current (IB) from a known kVA/kW rating — that current is exactly the input the Fuse & Breaker Sizing tool needs to select an appropriately rated protective device.